Mounting

LSM-2020’s are contained in a potted plastic case and may be mounted in any convenient position. The
construction of an LSM-2020 is durable enough to mount directly on a genset using ¼-inch hardware.
Hardware selection should be based on any expected shipping/transportation and operating conditions.
The torque applied to the mounting hardware should not exceed 65 in-lb (7.34 N•m).

See Figure 9-3 for LSM-2020 overall dimensions. All dimensions are shown in inches with millimeters in
parenthesis.

Figure 9-3. LSM-2020 Overall Dimensions

Connections

LSM-2020 connections are dependent on the application. Incorrect wiring may result in damage to the
module.

NOTES

Operating power from the battery must be of the correct polarity. Although
reverse polarity will not cause damage, the LSM-2020 will not operate.

Be sure that the LSM-2020 is hard-wired to earth ground with no smaller than
12 AWG copper wire attached to the chassis ground terminal on the module.

Terminations

There are two types of interface terminals: plug-in connectors with screw-down compression terminals
and an RJ-45 socket.

5.50 [139.7]

6.38 [162.0]

7.50 [190.5]

8.38 [212.8]

1.39 [35.3]

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

9-6

DGC-2020 LSM-2020 (Load Share Module)