Terminal

Description

P2-5 (LS–)

Load share line negative

P2-4 (LS’)

Provides additional landing point for external resistor

CAN bus Interface

These terminals provide communication using the SAE J1939 protocol and provide high-speed
communication between the LSM-2020 and the DGC-2020. Connections between the LSM-2020 and
DGC-2020 should be made with twisted-pair, shielded cable. CAN bus interface terminals are listed in
Table 9-4. Refer to Figure 9-6 and Figure 9-7.

Table 9-4. CAN bus Interface Terminals

Terminal

Description

P2-12 (CAN L)

CAN low connection (green wire)

P2-11 (CAN H)

CAN high connection (yellow wire)

P2-10 (SHIELD)

CAN drain connection

NOTES

1. If the LSM-2020 is providing one end of the J1939 bus, a 120

Ω, ½ watt

terminating resistor should be installed across terminals P2-12 (CANL)
and P2-11 (CANH).

2. If the LSM-2020 is not part of the J1939 bus, the stub connecting the LSM-

2020 to the bus should not exceed 914 mm (3 ft) in length.

3. The maximum bus length, not including stubs, is 40 m (131 ft).

4. The J1939 drain (shield) should be grounded at one point only. If

grounded elsewhere, do not connect the drain to the LSM-2020.

Figure 9-6. CAN bus Interface with LSM-2020 providing One End of the Bus

AEM-2020

(Optional)

LSM-2020

Other

Devices

P0053-58

Engine

120 ohm

Termination

CAN-H

CAN-L

CEM-2020

(Optional)

DGC-2020

120 ohm

Termination

Bus

Stub

9400200990 Rev X

DGC-2020 LSM-2020 (Load Share Module)

9-9

Advertising