3. Second-UPS

S-UPS: capacitive seconds UPS

The CX50x0 family features a built-in capacitive one-second UPS. It ensures a safe storage of the persistent
application data on the Compact Flash card.

Up to 1 MB of data can be saved. The UPS can be switched on and off via the BIOS:

Phoenix - AwardBIOS CMOS Setup Utility

PC Health Status

SUSV

[Enabled]

Item Help

SUSV holds USB

[Enabled]

SUSV Status

100% Cap. / Charging

On Die Digital Temp.

47°C

Temp. Board

56°C

Temp DDR

57°C

CPU Core

1.07V

SCH Core

1.04V

...

SUSV

Option for deactivating the one-second UPS.

SUSV holds USB

If system buffering based on SUSV is active, this option can be used to switch the power supply for the USB port on
or off. This is important for data back-up on a USB storage medium, for example.

SUSV Status

This value indicates the status of the one-second UPS.

n% Cap. (n={0..100}) indicates the capacity of the UPS.

State (charging / discharging) describes the state of the one-second UPS.

Integration into a PLC

TwinCAT offers special function blocks for integrating the S-UPS into a PLC program. These are described below.
From TwinCAT 2.11R2 Build 2016 the required library is integrated in the installation. For older versions the library
TcSUPS.lib has to be copied into the TwinCAT library directory.