Notes on the documentation

36

CX50x0 - Hardware Documentation

RS422/RS485 connections (CX50x0-N031)

The CX50x0-N030 system interface provides an RS422 or RS 485 interface, COM1 (X300). It is implemented on a 9-
pole Sub-D socket strip. If more than one interface is required the system can be extended via the Terminal Bus (K-
or E-bus) or Bus Terminals (KL/EL6021) which provide serial interfaces. The pin assignment is shown at the bottom
of the page.

The maximum baud rate on both channels is 115 kbit. The interface parameters are set via the operating system or
from the PLC program.

COM interface (socket)

Pin assignment of the COM interface

PIN

Signal

Typ

Beschreibung

2

TxD+

Data-Out +

Transmit 422

3

TxD+

Data-In +

Receive 422

5 GND

Ground

Ground

6

VCC VCC +5V

7

TxD-

Data-Out -

Transmit 422

8 TxD+

Data-In

-

Receive

422

For RS 485 pins 2 and 3 (data +) must be connected, and pins 7 and 8 (data -).

Setting of interface parameter

RS485, without echo, end-point (termination) default setting

Function

Status

Echo on

Off

Echo off

On

Auto send on

On

Always send on

Off

Auto receive on

On

Alway receive on

Off

Term on

On

Term on

On

Note

Change the parameter

If there is a need for other settings please contact our service department.