Leds for k-bus diagnosis, Leds of the k-bus-power supply unit (cx50x0-1xxx) – BECKHOFF CX50x0 User Manual

Page 69

Advertising
background image

Notes on the documentation

CX50x0 - Hardware Documentation

67

LEDs of the K-bus-power supply unit (CX50x0-1xxx)

After switching on, the power supply immediately checks the connected Bus Terminal configuration. Error-free start-
up is signaled by the red "I/O ERR” LED being extinguished. If the ”I/O ERR" LED blinks, an error in the area of the
terminals is indicated. The error code can be determined from the frequency and number of blinks. This permits rapid
rectification of the error.

Display

LED

Meaning

Us 24
V

Power supply for the CPU module
The LED lights green if the power supply is correct.

Up
24V

Power supply for terminal bus.
The LED lights green if the power supply is correct.

K-BUS
RUN

K-Bus diagnostics
The green LED lights up in order to indicate fault-free
operation. "Fault-free" means that the communication
with the fieldbus system is also running.

K-BUS
ERR

K-Bus diagnostics
The red LED flashes to indicate an error. The red LED
blinks with two different frequencies.

The I/O error LED blink code

fast blinking

Start of the error code

first slow sequence

Error code

second slow sequence

Error code argument

LEDs for K-Bus diagnosis

Error code

Error code
argument

Description

Remedy

Persistent,
continuous
flashing

EMC problems

Check power supply for overvoltage or
undervoltage peaks

Implement EMC measures

If a K-Bus error is present, it can be lo-
calised by a restart of the power supply
(by switching it off and then on again)

1 pulse

0

EEPROM checksum error

Revert to the manufacturer’s setting

1

Code buffer overflow

Insert fewer Bus Terminals. Too many entries in
the table for the programmed configuration

2

Unknown data type

Software update required for the power supply

2 pulses

0

Programmed configuration
has an incorrect table entry

Check programmed configuration for
correctness

n (n > 0)

Table comparison (Bus
Terminal n)

Incorrect table entry

3 pulses

0

K-Bus command error

No Bus Terminal inserted

One of the Bus Terminals is defective;
halve the number of Bus Terminals at-
tached and check whether the error is
still present with the remaining Bus
Terminals. Repeat until the defective
Bus Terminal is located.

4 pulses

0

K-Bus data error, break
behind the power supply

Check whether the n+1 Bus Terminal is correctly
connected; replace if necessary.

n

Break behind Bus Terminal
n

Check whether the Bus End Terminal 9010 is
connected.