Blower Motor Will Not Run

Does Blower Wheel

Spin Freely

115 Volts at

Furnace

115 Volts at Motor

Connector

Check Fuses

Disconnect 16 Pin

Signal Connector

From Motor

24VAC BetweenPins

1 - 12
2 - 12

No

No

Yes

No

Yes

Yes

No

No

Blower Rubbing

Against Housing

Repair or

Replace Wheel

Replace Motor

Yes

No

Verify Correct

Furnace Wiring

Repair Wiring

Replace Power

Cord

Yes

24 Volts R-C on

T erminal Strip

Yes

Replace

Fan Center Relay

No

Check Wiring
Replace Cable

Place Jumper on

R-W

24VAC

BetweenPins

1 - 2

Check Wiring
Replace Cable

Place Jumper on

R-Y

24VAC

BetweenPins

1 - 6

Check Wiring
Replace Cable

Place Jumper on

R-G

24VAC

BetweenPins

1 - 15

Check Wiring
Replace Cable

Check Pins in Connector

and Motor. Reconnect

Signal Connector

Connections are

Good

Replace Cable

Replace Motor

Yes

No

No

No

No

No