Heating:

1300 CFM per 100,000 Btuh output

Cooling:

400 CFM per ton of air conditioning

Determine the required air flow for the system based on both heating and cooling requirements. Use

the larger of either for duct design.

Table 3 lists the maximum recommended air velocities for ducts. Velocities greater than those as

listed may result in objectionable air noise in the ducts.

Table 3 Recommended Maximum Duct Velocities, Feet Per Minute (FPM)

Main Ducts*

Branch Ducts

Application

Supply Return Supply Return

Apartments

900

700

600

600

Auditoriums 1200 1000 1000 800
Banks

2000

1500

1600

1200

Hotel

Rooms

1500 1300 1200 1000

Libraries

2000

1500

1600

1200

Meeting

Rooms

2000 1500 1600 1200

Offices

2000

1500

1600

1200

Residences 900 700 600 600
Restaurants

2000

1500

1600

1200

Retail

Stores 2000 1500 1600 1200

*When sound control is critical use branch duct velocities


Table 4 Duct Area Required at Listed Flow Conditions

CFM Area

Sq. In.

600FPM

Area

Sq. In.

800FPM

Area

Sq. In.

1000FPM

Area

Sq. In.

1200FPM

Area

Sq. In.

1600FPM

Area

Sq. In.

2000FPM

50

12

100

24 18 14 12

150

36

27

22

18

14

200

48 36 29 24 18 14

250

60

45

36

30

23

18

300

72 54 43 36 27 22

400

96

72

58

48

36

29

500

120 90 72 60 45 36

750

180

135

108

90

68

54

1000

240 180 144 120 90 72

1250

300

225

180

150

113

90

1500

360 270 216 180 135 108

1750

420

315

252

210

158

126

2000

480 360 288 240 180 144

Note: For Systems not over 100 feet equivalent length. Do not apply this table to duct systems
which exceed 100 equivalent feet in length. For longer systems refer to ACCA Manual D.
Incorrectly sized ducts can result in unsafe or uncomfortable operation.