D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

3-294

Program Example:

Connect PLC to VFD series AC motor drive (RTU mode, M1143 = ON), (8-bit mode, M1161 =

ON), Write the data to be sent (H1770) into address H0706 on VFD.

M1002

MOV

H86

D1120

SET

M1120

Sending
request pulse

Write data to be sent in advance

SET

M1122

MOV

K100

D1129

X0

RS

D100

K8

D120

K8

Processing received data

RST

M1123

M1123

Receiving completed

Set communication protocol as
9600,7,E,1

Retain communication setting

Set communication timeout as:
100ms

Sending request

Reset M1123

SET

M1161

8-bit mode

PLC VFD, PLC sends: 01 06 0706 1770 66 AB

Registers for sent data (sending messages)

Register Data

Explanation

D100 low byte

01 H

Address

D101 low byte

06 H

Function

D102 low byte

07 H

D103 low byte

06 H

Data address

D104 low byte

17 H

D105 low byte

70 H

Data content

D106 low byte

66 H

CRC CHK 0

D107 low byte

AB H

CRC CHK 1

The error checksum CRC CHK (0,1) can be calculated by CRC instruction (8-bit mode, M1161 =

ON).

M1000

CRC

D100

K6

D106

CRC checksum: 66 H is stored in low byte of D106 and AB H in low byte of of D107,