Delta DVP-ES2 User Manual

Page 463

Advertising
background image

3 . I n s t r u c t i o n S e t

3 - 3 4 7

ASCII mode (COM3: M1320 = OFF, COM1: M1139 = OFF):

When X0 = ON, MODRW instruction executes the function specified by Function Code 05

PLC1

Ö PLC2, PLC sends: “01 05 0500 FF00 6F

PLC2

Ö PLC1, PLC receives: “01 05 0500 FF00 6F

(No data processing on received data)

RTU mode (COM3: M1320 = ON, COM1: M1139 = ON):

When X0 = ON, MODRW instruction executes the function specified by Function Code 05

PLC1

Ö PLC2, PLC1 sends: “01 05 0500 FF00 8C F6

PLC2

ÖPLC1, PLC1 receives: “01 05 0500 FF00 8C F6

(No data processing on received data)

Program Example 7: COM2(RS-485), Function Code H06

1.

Function code K6 (H06): Write in single word device.

2.

Set the value to be written into VFD-B in the register specified by operand S.

3.

For ASCII or RTU mode, PLC COM2 stores the data to be sent in D1256~D1295, and

received data in D1070~D1085.

4.

Take the connection between PLC (PLC COM2) and VFD-B for example, the tables below

explains the status when PLC reads status of VFD-B. (M1143 = OFF, ASCII Mode) (M1143 =

ON, RTU Mode)

H87

MOV

M1002

D1120

SET

M1120

K100

MOV

D1129

RST

M1127

Set communication protocol as 9600, 8, E, 1

Retain communication protocol

Set communication timeout as 100ms

MODRW

K6

K1

X0

H2000

D50

K1

Connection device
address: K1

Function code K6
write in single data

Data address: H2000

Data storing register
D50=H1770

Data length

Processing received data

ASCII mode: The received data is stored in D1070~D1085 in ASCII format

RTU mode: The received data is stored in D1070~D1085 in Hex format

Reset M1127

M1127

SET

X0

M1122

Sending request

M1143 = OFF

ASCII mode

RST

M1143

M1143 = ON
RTU mode

SET

M1143

Receiving completed

Advertising
This manual is related to the following products: