3 . I n s t r u c t i o n S e t

3 - 3 2 9

API Mnemonic

Operands

Function

148

MEMR

P

Reading the data
from the file register

Controllers

ES2/

EX2

SS2

SA2 SX2

SE

Bit Devices

Word devices

Program Steps

Type

OP

X Y

M S K H KnX KnY KnM KnS T C D E F

m

*

*

*

D

*

n

*

*

*

7 steps

The 32-bit instruction and
DVP-SS2 are not
supported.

PULSE 16-bit 32-bit

ES2/

EX2

SS2 SA2 SX2 SE

ES2/

EX2

SS2 SA2 SX2 SE

ES2/

EX2

SS2 SA2 SX2 SE

Operands:

M: File register from which the data is read (The value is between K0 and K4999.) D: Initial data

register where the data is stored (The data register is between D2000 and D9999.) N: Number of

data (The number of data is between K1 and K5000.)

Explanations:

1.

There are 5,000 16-bit file registers. The register numbers range from K0 to K4999.

2.

The 32-bit instruction is not supported.

3. If

m, D, or n is not within the range, an operation error occurs, the instruction is not executed,

M1067 and M1068 is ON, and the error code in D1067 is H’0E1A.

4.

If no data is written into the file register, the default value which will be read from it is -1.

5.

DVP-ES2/EX2/SS2 version 2.80 and above, DVP-SA2/SX2 version 2.40 and above are

supported. The instruction is not applicable to DVP-ES2-C.

6.

The file registers do not support M1101. If users want to read the data from the file register

when the PLC runs, they can use LD M1002 and MEMR to read the data.

Program Example:

1.

Use MEMR to read the data from the 100 file registers starting from the tenth file register to the

data registers starting from D2000.

2.

When X0 is ON, the instruction is executed. When X0 becomes OFF, the instruction is not

executed, and the data which is read previous is unchanged.

X0

MEMR

K10

D2000

K100