3 . I n s t r u c t i o n S e t

3 - 4 3 9

API Mnemonic

Operands

Function

197

D CLLM

Close loop position
control

Controllers

ES2/EX2 SS2 SA2

SE

SX2

Bit Devices

Word devices

Program Steps

Type

OP

X Y

M S K H KnX KnY KnM KnS T C D E F

S

1

*

*

S

2

*

*

*

S

3

*

*

*

D

*

DCLLM: 17 steps

PULSE 16-bit 32-bit

ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2

Operands:

S

1

: Feedback source device S

2

: Target number of feedbacks S

3

: Target frequency of

output D: Pulse output device

Explanations:

1. The corresponding interrupt pointers of S

1

:

Source device

X4

X6

C243 ~ C254

Associted outout

Y0 Y2 Y0 Y2

No. of Interrupt pointer

I40

I60

I010

I050

… = 1: rising-edige triggered; … = 0: falling-edge triggered

a) When

S

1

designates input points X and the pulse output reaches the target number of

feedbacks in S

2

, the output will continue to operate by the frequency of the last shift (end

frequency) until interrupts occur on input points X.

b) When

S

1

designates high speed counters and the pulse output reaches the target

number of feedbacks in S

2

, the output will continue to operate by the frequency of the

last shift (end frequency) until the feedback pulses reaches the target number.

c) S

1

can be a high speed counter C or an input point X with external interrupt. If S

1

is C,

DCNT instruction should be executed in advance to enable the high-speed counting

function, and EI instruction with I0x0 should be enabled for external interrupts. If S

1

is X,

EI instruction with I0x0 should be enabled for external interrupts.

d) If S

1

is specifed with counters, DHSCS instruction has to be programmed in user

program. Please refer to Program example 2 for details.

2. Range

of

S

2

: -2,147,483,648 ~ +2,147,483,647 (+ / - indicates the positive / negative rotation

direction). the present value of pulse output in CH0 (Y0, Y1) and CH1 (Y2, Y3) increases in

positive direction and decreases in negative direction. Registers storing present value of

pulse output: CH0(D1031 High, 1030 Low), CH1(D1337 High, D1336 Low)

3. If

S

3

is lower than 6Hz, the output will operate at 6Hz; if S

3

is higher than 100kHz, the output

will operate at 100kHz.