D V P - E S 2 E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

5.6 IST

Instruction

API Mnemonic

Operands

Function

Controllers

ES2/EX2

60

IST

Initial State

SS2 SA2 SX2

Bit Devices

Word devices

Program Steps

Type

OP

X Y M S K H

KnX

KnY KnM KnS T C D E F IST: 7 steps

S

* * *

D

*

1

D

*

2

PULSE 16-bit 32-bit

ES2/EX2 SS2 SA2 SX2 ES2/EX2 SS2 SA2 SX2 ES2/EX2 SS2 SA2 SX2

Operands:

S: Source device for assigning pre-defined operation modes (8 consecutive devices). D

1

The

smallest No. of step points in auto mode. D

2

: The greatest No. of step points in auto mode.

Explanations:

1.

The IST is a handy instruction specifically for the initial state of the step ladder operation

modes.

2.

The range of D

1

and

D

2

: S20~S911, D

1

< D

2

.

3.

IST instruction can only be used one time in a program.

Program Example 1:

M1000

IST

X20

S20

S60

X20: Individual operation (Manual operation)

X24: Continuous operation

S:

X21: Zero return

X25: Zero return start switch

X22: Step operation

X26: Start switch

X23: One cycle operation

X27: Stop switch

1.

When IST instruction is executed, the following special auxiliary relays will be assigned

automatically.

M1040: Movement inhibited

S0: Manual operation/initial state step point

M1041: Movement start

S1: Zero point return/initial state step point

M1042: Status pulse

S2: Auto operation/initial state step point

M1047: STL monitor enable

2.

When IST instruction is used, S10~S19 are occupied for zero point return operation and

cannot be used as a general step point. In addition, when S0~S9 are in use, S0 initiates

5-22