User Instructions - Logix® 500+ Series Digital Positioners FCD LGENIM0105-10 11/13

flowserve.com

52


18.3

Status Code Descriptions

NOTE: Not all status codes are available with all

positioner models.

GGGG

●●●●

POWER ON

Description: No issues.

Possible Solutions: Not applicable.

GGGY

●●●

TIGHT SHUT OFF MODE

Description: (Also called MPC.) The Final Command is
beyond the user set limit for the tight shutoff feature and the
positioner is applying full actuator pressure to close (or open)
the valve. This is a normal condition for all valves when
closed. The factory default setting triggers this at command
signals below 1%. This indication may also occur on 3 way
valves at both ends of travel if the upper Tight Shut Off value
has been set.

Possible Solutions: If tight shutoff is not desired reset the
tight shutoff limits or adjust the command signal inside of the
specified Tight Shut Off values.

GGYG

●●

LOCAL INTERFACE OFF

Description: Control and configuration features are locked at
the positioner's local interface. This is to prevent
unauthorized or accidental adjustments. The buttons can still
be used to view information on the LCD. The status code is
only present for a short time when the user attempts to make
a change through the display menu.

Possible Solutions: The DTM's Local Interface page is used
to unlock the local interface, turn this feature on and off, and
to set the PIN. For temporary access, a Personal
Identification Number (PIN) can be entered from the
positioner if an LCD is installed.

GGYY

●●

●●

DIGITAL COMMAND MODE

Description: The input command is set by a digital HART
command instead of the 4-20 mA signal.

Possible Solutions: The input command source can be
changed back to the 4-20 mA signal by using a handheld, the
Dashboard page of the DTM, or performing a manual
Command Reset. Perform the Command Reset by holding
both the UP and DOWN buttons and briefly pressing the
QUICK-CAL/ACCEPT button.

GGYR

●●

INITIALIZING

Description: The positioner has powered up and is displaying
a blink sequence 3 times.

Possible Solutions: Wait for 3 blink sequences to complete.

GGRR

●●

●●

SQUAWK MODE


Description: A user has set the positioner to flash a special
sequence so that it can be visually located.

Possible Solutions: This mode is cancelled if one of the
following occurs: 1) The QUICK-CAL/ACCEPT button is
briefly pressed. 2) The Squawk mode is turned off remotely.
3) More than one hour has passed since the command was
issued.

GYGY

SOFT STOP HIGH LIMIT ALERT
SOFT STOP LOW LIMIT ALERT

Description: The Final Command would move the valve
beyond the user-set Soft Limit, but the internal software is
holding the position at the limit. The function is similar to a
mechanical limit stop except it is not active if the unit is un-
powered.

Possible Solutions: If more travel is needed, reset the Soft
Limits. If not, adjust the Final Command signal back into the
specified range.

GYYG

●●

PRESSURE CALIBRATION REQUIRED

Description: A Factory Pressure Calibration has not been
performed. Unlike a regular pressure sensor calibration, a
Factory Pressure Calibration saves the calibration values to
memory, making them available should a factory reset be
performed. Proper pressure sensor calibration is required for
proper pressure sensing and diagnostics. Calibration values
from a regular pressure sensor calibration will be lost when a
factory reset is performed. Typically no pressure calibration
is required with a new positioner.

Possible Solutions: After replacing a main board or a
pressure sensor board, perform a Factory Pressure
Calibration. To do this, see the Pressure Sensor Board
Removal and Installation section of the IOM.

GYYY

●●●

FRICTION CALIBRATION REQUIRED

Description: No friction calibration has been performed since
the last factory reset. The friction calibration determines a
preliminary friction value, spring forces and direction and
other information used for proper diagnostics. If no friction
calibration is performed, the positioner will soon determine
the operating friction, but other diagnostic information will be
missing.

Possible Solutions: Perform a Friction Calibration using the
display menu, handheld, or Sensor Calibration page of the
DTM. See the Calibration section of the IOM for warnings.

GYYR

●●

PARTIAL STROKE TEST SCHEDULED

Description: The schedule established by the user shows that
a partial stroke test is due.

Possible Solutions: Follow internal procedures to initiate a
partial stroke test (PST). A partial stroke test will cause the
valve to move suddenly and the positioner will not respond to
commands while the PST is in progress. See the Partial
Stroke Test page of the DTM to verify PST settings.