SMB Series/SB Series Installation and Maintenance FCD LMENIM1401-04-AQ – 01/15

14

4.3.3 Terminal Connections

Wiring connections to the SMB geared limit switch, torque switch, and Marathon terminal strips are
to be made using ring-tongue terminals* as shown below:

Figure 4.1 – Wiring Connections

A

C

B

Table 4.3– Terminal Connections

AWG

Screw Hole

Insulation

Thomas &

Betts P/N

A

B

C

22-16

#10

Vinyl

18RA-10

.97

.31

.27

18-14

#10

Vinyl

14RB-10

.97

.31

.27

12-10

#10

Vinyl

14RC-10

1.06

.31

.27

Note: Limit switch and torque switch contacts are rated 300 volts per NEMA ICS-2

Terminals are to be crimped using Thomas & Betts crimping tool WT112M or ERG4001.

Manufacturer: *Thomas and Betts or equal

4.4 Setting The Limit Switch

c

WARNING: Disconnect all incoming power before opening or replacing the limit switch compart-
ment cover.

a

CAUTION: When wiring control circuits, distinguish between “normally open” and “normally
closed” terminals on the geared limit switch.

a

CAUTION: Do NOT attempt to repair the limit switch gear box. Replace entire limit switch gear
box.

a

CAUTION: Do NOT use abrasive cloth to clean the silver contacts on the limit switch. Contacts
should be burnished using appropriate burnishing tool.

a

CAUTION: Before motor operation, reset the geared limit switch if the actuator has been
dismantled or removed from the valve.

NOTE: Clean the limit switch cover thoroughly and apply a thin coat of grease on machined flange
surfaces before mounting on an explosion proof actuator.