7.14.10 Stroke Length

Stroke length is used by the travel accumulator. When the stroke length and units are set, the length
is used to determine the total travel accumulated. The travel accumulator will have the units associ-
ated with stroke.

ExAMPLE: Stroke length is set to four inches. If the valve is moved from 0 percent to 100 percent,
four inches will be added to the travel accumulator. The travel accumulator units will be inches. If
Stroke length is 90 degrees for a rotary, the travel accumulator will now have units of degree. A 0
percent to 100 percent stroke will add 90 to the travel accumulator.

NOTE: Stroke length is for information only and is not used during calibration.

Table IX: Transducer Block Characterization Parameters

Parameter

Description

Value - Meaning

Comments

MODE_BLK

The operating mode

of the transducer

block

Auto - Auto (target mode) The transducer

block must be out

of service before

characterization

can be edited or

changed

OOS - Out of Service

CONTROL_

FLAGS

Byte values which

select positioner

operation features

1 - Quick Opening Curve* Loads factory-

defined QO curve as

custom curve.

2 - Equal Percent Curve*

Loads factory-

defined equal

percent curve as

custom curve.

3 - Actuator Type

4 - Advanced Model

5 - Rotary Actuator Gain

6 - Custom

Characterization Active

Activates custom

curve. If Off,

response is Linear.

7 - Fail Position TBD

8 - Air Action

CURVEX

Numeric X value

array for custom

point. (1 x 21 array

points)

X-axis value for custom

stroke characterization

point. Range –10 to 110

Pair each X-value

with corresponding

Y-value to define

the desired point.

Values must be

in ascending (or

equal) order.

CURVEY

Numeric Y value

array for custom

point. (1 x 21 array

points)

Y-axis value for custom

stroke characterization

point. Range –10 to 110

*NOTE: Must not be selected if a custom curve is to be created or edited.