The spool valve chamber (see Figure 21) must also be vented through the spool valve cover.
Vented-design Logix 3400IQ positioners are supplied from the factory with a fitting installed in the
spool valve cover (item SKU 179477). Connect the necessary tubing/piping to this fitting to route
the exhausted natural gas to a safe environment. The maximum allowable back pressure in the spool
valve chamber is 8 psig (0.55 barg). Pressures greater than 8 psig will cause vented gas to leak past
the spool cover O-ring to the atmosphere and will result in overshoot of the positioner.