Flowserve Desuperheaters User Manual

Page 15

Advertising
background image

15

Desuperheaters FCD VLENIM0115-00 – 09/11

flowserve.com

Table 5: Dimensions for Reassembly of Retainer

Model Number

Dimension A

(in)

Dimension B

(nozzle stroke)

(in)

Nozzle Mounting

Thread Torque Value

(ft-lbs / Nm)

MCX 025

0.228

0.016 ± .002

30 / 41

MCX 050

0.558

0.032 ± .002

50 / 68

MCX 075

1.000

0.039 ± .002

90 / 122

MCX 100

1.056

0.047 ± .002

200 / 271

MCX 125

1.245

0.055 ± .002

300 / 407

MCX 150

1.478

0.062 ± .002

500 / 678

MCX 175

1.623

0.070 ± .002

600 / 813

MCX 200

1.876

0.078 ± .002

800 / 1085

Figure 13: View of MaxCool MCX tack weld

VaporCool
Follow steps 1-14 and refer to Figure 14 to clean or replace the VaporCool desuperheater.

1. Depressurize the steam line, drain the cooling water line and disconnect the cooling water line

from the desuperheater. Remove the desuperheater from the steam line.

2. Carefully grind off the tack welds between the nozzle head and the lance pipe connection.

3. Unscrew the nozzle head off of the lance pipe connection.

4. Carefully grind off the tack welds between the nozzle head case and the nozzle head face.

5. Secure the large nozzle head face hex flats in a vice and unscrew the nozzle head case by turning

the small hex flats, leaving the nozzle head face in the vice.

6. With a straight screwdriver, unscrew each of the seven nozzles from the nozzle head face.

7. If cleaning is required: With compressed air blow out the passageways of the nozzles and clean

the nozzle mounting cavity. Inspect each hole in the nozzles as well as the nozzle head face for
contamination and blockage. Replace the nozzles and tighten with a screwdriver.

Tack Weld on

Nozzle Pipe