Technical data – Flowserve LRR1-40 TDS Control Unit User Manual

Page 10

Advertising
background image

10

Explanatory Notes

– co ntinued –

Technical data

Type approval no.

TÜV.WÜL.02-007
EG BAF- MUC 02 05 103881 003

Input /Output

Interface for CAN bus to ISO 11898 CANopen.

Inputs

CAN bus interface with power supply 18- 36V DC, short circuit protected.
Analog control input for indicating valve position via feedback potentiometer 1000

,

angle of rotation 320°, supply voltage 5V DC.
Voltage input 18-36V AC (50/60 Hz) or DC for external command:
Control OFF, valve CLOSED, intermittent blowdown OFF. With DC protected against
polarity reversal.

Outputs

Four volt-free relay contacts.
Max. contact rating with a switching voltage of 24V AC /DC, 115 V AC and 230 V AC:
resistive / inductive 4A.
Contact material AgNi 0.15.
Current output 4-20mA as actual value output, max. load 750

(optional).

Conductivity measuring range with actual value output 4- 20mA

* based at 25°C

Beginning of measuring range

End of measuring range

ppm*

µS /cm *

m A

ppm *

µS /cm *

mA

0.25

0.5

4

10

20

20

50

100

20

100

200

20

250

500

20

500

1000

20

1000

2000

20

3000

6000

20

6000

12000

20

Note

The electrical conductivity is measured in µS/cm. For ppm (parts per million)
use the following conversion:
1µS/cm = 0.5ppm.