Explanatory Notes

– co ntinued –

Technical data

- co ntinu ed -

24 hr purging pulse

Forced opening of the continuous blowdown valve every 24 hours, adjustable.

Automatic intermittent blowdown

Interval time (duration of break): 1-120 hours, adjustable in steps of one hour.
Duration of pulse: 1-60 seconds, adjustable in steps of one second.

Mains supply

230V + 10 / -15%, 50- 60 Hz
115V + 10 / -15%, 50- 60 Hz (optional)
24V + 10 / - 15%, 50-60 Hz (optional)

Power consumption

10 VA

Protection

Casing: IP 40

to

EN 60529,

Terminal strip

IP 20 to EN 60529.

Admissible ambient temperature

0-55° C

Casing

Design:

Case made of insulating material, with plug-in terminals

Casing material:

Base: black polycarbonate; front panel: grey polycarbonate,

Number of terminals:

30

Cross section of connector: 1x 4.0 mm

2

solid or

1x 2.5 mm

2

stranded wire with sleeve to DIN 46228 or

2 x 1.4 mm

2

stranded wire with sleeve to DIN 46228,

Fixing of conductor:

Plus/ Minus terminal screw M 3.5,
Terminals with self-lifting wire protection.

Terminal strip:

Separately detachable,

Fixing of casing:

Mounting clip on supporting rail TH 35, EN 60715.

Weight

Approx. 0.8 kg