32

Malfunctions

Fault finding list for troubleshooting

Equipment does not work - no function

Fault:

LED "Power"

is not illuminated.

Remedy:

Switch on power supply and wire equipment in accordance with the wiring
diagram.

Equipment does not work correctly

Fault:

The connected actual value indicator shows incorrect values.

Remedy:

Dirt deposits on the conductivity electrode. Remove the equipment and
clean the measuring surface.

Fault:

A MIN or MAX limit alarm is given although the actual value (reference
measurement) lies within these limits.

Remedy:

Dirt deposits on the conductivity electrode. Remove the equipment and
clean the measuring surface.

If configured as proportional controller: The equipment works as two-position
(on - off) controller

Fault:

The feedback potentiometer in the continuous blowdown valve is either
defective or not connected.

Remedy:

Wire the equipment in accordance with the wiring diagram and check the
potentiometer.