3 output circuits specifications, 4 input circuit characteristics, 5 controls – all models – Flowserve AF-17 Electronic Positioner User Manual

Page 21: Worcester controls

Advertising
background image

WCAIM2031

AF-17 Electronic Positioner: Installation, Operation and Maintenance

21

6.3 Output Circuits Specifications

All Models

Maximum Surge Current ...............................................100 amps for 1 cycle

Maximum Normal Starting or In-Rush Current ............10 amps for 1 second

Maximum Stall Current ..................................................8 amps for 1 minute

Maximum Running Current – Resistive Load......................................5 amps
90% Duty Cycle

Maximum Running Current – Inductive Load......................................3 amps
90% Duty Cycle

Maximum Peak Voltage on Load Circuit ............................................800 VAC
All 120 VAC and 240 VAC

4-20 mA output will drive 20 mA into a 600 ohm maximum load.

6.4 Input Circuit Characteristics

6.4.1 Input Circuit Load Resistances

Approximate

1 to 5 milliamp Models .......................................................................1000 ohms

4 to 20 milliamp Models .......................................................................220 ohms

10 to 50 milliamp Models .....................................................................100 ohms

0 to 5 VDC Models................................................................................800 ohms

0 to 10 VDC Models............................................................................1100 ohms

6.4.2 Nominal Useable Input Signal Deadband

1000 ohm Input .....................................................................................5.5 ohms

135 ohm Input..................................................................................... .75 ohms

1 to 5 milliamp Input.................................................................20 microamperes

4 to 20 milliamp Input...............................................................80 microamperes

10 to 50 milliamp Input...........................................................200 microamperes

0 to 5 VDC Input................................................................................25 millivolts

0 to 10 VDC Input..............................................................................50 millivolts

NOTE: Above “Useable” deadband figures are “NORMS” determined by multiple tests of various actuator/valve
combinations. All actuators used a permanent split phase motor, with an output shaft speed of 1 RPM (15-second
cycle time). Electronic braking was employed on all tests. Results may differ in applications where different shaft
speeds are used.

6.5 Controls – All Models

Zero – Adjustment for Low End of Control Signal +60% Span

Range – Adjustment for High End of Control Signal -60% Span

AH – Adjustment for Hysteresis (Anti-Hunt) 0.3% to 4.0% of full scale

4 mA – Adjust 4 mA Output

20 mA – Adjust 20 mA Output

Flow Control Division