2 symptom table, Worcester controls – Flowserve AF-17 Electronic Positioner User Manual

Page 24

Advertising
background image

24

AF-17 Electronic Positioner: Installation, Operation and Maintenance

WCAIM2031

8.2 Symptom Table

Test Unit for Milliamp Input Positioner – Set R1 all the way toward the plus end. Adjust R2 for a 20 mA reading. Varying R1 will
now provide input signals between 4 and 20 milliamps.

Sympton

Guidlines to Follow

8.2.1

Actuator will not operate in either direction

8.3.1, 8.3.2, 8.3.3, 8.3.4, 8.3.5, 8.3.6, 8.3.7,

[no sound from motor(s)].

8.3.10

8.2.2

Actuator will not operate in either direction

8.3.2, 8.3.3, 8.3.4, 8.3.5, 8.3.6, 8.3.9, 8.3.10,

[humming or buzzing sound from motor(s)].

8.3.11, 8.3.12

8.2.3

Actuator slowly moves in one direction on its own.

8.3.4

8.2.4

Actuator runs normally for 7° to 8° while coming off

8.3.4, 8.3.15

limit switch, then slows down or stops
[motor(s) hum or buzz].

8.2.5

Actuator oscillates intermittently or upon

8.3.2, 8.3.8, 8.3.13

reaching a new position.

8.2.6

Actuator runs slowly in one or both directions, .

8.3.2, 8.3.4, 8.3.9, 8.3.10, 8.3.11, 8.3.12

but otherwise operates normally

8.2.7

Actuator works intermittently.

8.3.2, 8.3.10, 8.3.12

8.2.8

Actuator runs normally in one direction but will not

8.3.2, 8.3.4, 8.3.7

operate in the other direction
[no hum or buzz from motor(s)].

8.2.9

Actuator will not move valve after a stop when signaled

8.3.14

to travel in same direction as previous command.

Flow Control Division

Worcester Controls

Figure 11