Troubleshooting - remote dial touch remote, Touch remote, Remote dial/touch remote assembly remote dial – Greenheck Vari-Green Motor (IOM 473681) User Manual

Page 7

Advertising
background image

7

Vari-Green Motor and Controls

Controls: Operation,
Wiring and Troubleshooting
Remote Dial/Touch Remote and
2-Speed Control

CAUTION

Even though the motor may not be operating,
high voltage power may still be present at the motor.
Make sure to disconnect power to the fan before
servicing.

Troubleshooting -
Remote Dial Touch Remote

Remote Dial does not adjust motor RPM

1. Check voltage to ensure the motor and transformer

are receiving the correct line voltage.

2. Check voltage at the remote dial. 24 VDC should

be present across the 24V and COM terminals.
0-10 VDC should be present across the 0-10V and
COM terminals.

3. Verify all of the connections at the transformer and

make certain that they are secure.

4. Touch remote: Verify that the touch remote is

unlocked.

Terminals

Desired Voltage

24V-COM

24 VDC Nominal

0-10V-COM

0-10 VDC

(varies with dial position)

Other Vari-Green

®

controls, such as the Constant

Pressure and Air Quality families of controls, have their
own manual that ship with the controller. They can also
be found on Greenheck.com. See table on page 9 for
document numbers.

Touch Remote

Follow installation instructions above. After Power is
applied to the system, operate as follows:

1. Touch power button to turn fan on.

2. Touch UP/DOWN arrow to increase/decrease speed.

3. Subsequent touches of the power button will start

the countdown timer of 90, 60, 30 or 10 minutes.

4. LED's will turn off after a periods of inactivity.

5. To lock/unlock buttons, hold the UP and DOWN

arrows for 3 seconds. When locked, the power
button will light up red.

White

Black

*

Red

Low voltage, route away

from high voltage lines

and/or use shielded cable

Factory Wiring

Field Wiring

115/230 VAC input

to match motor name plate

Green indiator light
—Power present

*

NOTE: Black wire not

used on some motors

2 x 4

Junction

Box

Remote Dial/Touch Remote Assembly

Trip Point = 1.85VDC
Contact Rating:
10A @ 24-240VAC
5A @ 30VDC

Auxiliary

Contact

COM

24V

0-10V

COM

24V

0-10V

N.C.

COM.

N.O.

Control

Motor

TRANSFORMER

REMOTE DIAL/

TOUCH REMOTE

0-10V

24V

COM

COM

24V

0-10V

100 ft. or less

Remote Dial/Touch Remote Assembly

Remote Dial

Installation Overview: The remote dial is provided
with the fan, shipped loose for remote installation.
It also includes a factory mounted 24 VDC transformer.

1. Disconnect power to the fan.

2. Identify where the remote dial will be mounted.

3. Mount a standard single-gang 2x4 junction box.

4. Run a 3-wire control cable from the remote dial

to the fan motor compartment. The maximum
distance from the fan to the remote dial is 100 feet.
If a greater distance is required, signal loss may
occur and cause the fan to operate erratically.

5. Connect control cable to transformer mounted

inside fan motor compartment. Connect control
cable to remote dial.

6. Secure remote dial to 2x4 junction box.

®

Advertising