Herrtronic MD General Applications

Engineering and Application

Herrtronic MD Series Steam Humidifiers can be applied in a variety of

applications. The simplest application consists of an “MD” unit and an

“RDU” (Room Distribution Unit). Steam is generated by the “MD” unit,

flows to the “RDU” unit, and is distributed in to the conditioned space.

As shown in Figure A, the “RDU” unit can be mounted on the MDS or

MDD units or remote mounted with any “MD” configuration. Steam input

is either into the bottom or rear of the “RDU” unit. In this application, only

the “RDU” needs to be in the conditioned space. One “RDU” is required

per “MDM” or “MDS” unit. Two “RDU” units are required for each “MDD”

unit.

Note: a condensate return line (provided) must be installed between the

“RDU” and “MD” units in the field.

Alternatively, steam generated by an “MD” unit can be discharged

directly into the system ductwork. In this application, steam distributor

pipe(s) are installed in the system ductwork with laminar airflow with

at least three (3) feet downstream clearance. Actual requirements

depend on your exact psychrometric conditions. Consult factory if you

should have any questions. If the blower operates intermittently, an air-

proving switch should be installed to insure blower operation prior to the

humidifier turning “on.” A high limit humidistat or sensor, located at least

10’ downstream of steam distributor, should be included for better system

control.

The number of steam outlets on the humidifier is as follows:

MDM – 1 outlet

MDS up to 50 lbs/hr. – 1 outlet

MDS up to 100 lbs/hr. – 2 outlets

MDD – 4 outlets.

A CS-58 Dual Outlet Adapter is available to convert to two (2) 1 ½” outlets

to a single 2” hose connection. Figures C1 and C2 reflect the spacing

required within the duct. Note: the standard steam distributors are sloped

to return condensate to the humidifier.

The steam piping from the humidifier to the steam distributor should have

a slope of +8% up to the steam distributor. Steam hose may be used to

a maximum of 20’ between the humidifier and the distributor. Beyond 20’,

system capacity is significantly reduced unless insulated copper pipe,

1-1/2 or 2” ID, is used. If there are any low spots between the humidifier

and the distributor, a condensate separator (such as EST-250) should

be used (Figure D). MDS and MDD system are designed for a maximum

of 7” duct static pressure. MDM units are designed for a maximum of 5”

duct static pressure. Consult the factory if you exceed these levels.

For applications requiring a short, guaranteed absorption distance,

consult the factory for selection of the appropriate CS Series steam

distribution system (Figure E).