Engineering Data:

Steam Output / Electrical Characteristics

Capacity:

Steam Output

Lbs/Hr

5

10

15

20

25

30

40

50

60

80

100

11

0

120

130

140

150

160

170

180

190

200

220

225

230

250

Kg/Hr

2.3

4.5

6.8

9.0

11.4

13.6

18.2

22.7

27.2

36.3

45.4

50

54.4

59.1

63.6

68.2

72.6

77.3

81.7

86.4

90.9

100

102.2

104.5

113.6

Input KW

1.7

3.3

5

6.6

8.3

10.0

13.3

16.7

20

26.6

33.3

36.6

40

43.3

46.6

50

53.3

56.6

60

63.3

66.6

73.3

75.3

76.6

83.3

Volts / Ph:

AMPS

208/1

8

16

24

32

40

48.1

64.1

240/1

6.9

13.8

20.8

27.6

34.7

41.7

55.6

69.4

208/3

4.6

9.2

13.9

18.5

23.1

27.8

37.0

46.3

55.5

74.0

92.6

101.7

110.9

120.2

129.4

138.6

147.9

157.1

166.4

175.6

184.9

240/3

4.0

8.0

12.0

16.0

20.0

24.1

32.1

40.1

48.1

64.2

80.2

88.1

96.1

104.2

112.2

120.2

128.2

136.2

144.2

152.2

160.2

480/3

2.0

4.0

6.0

8.0

10.0

12.0

16.0

20.0

24.0

32.1

40.1

44.1

48.1

52.1

56.1

60.1

64.1

68.1

72.1

76.1

80.1

88.1

90.5

92.1

100.1

600/3

1.6

3.2

4.8

6.4

8

9.6

12.8

16.0

19.2

25.6

32.1

35.2

38.5

41.7

44.9

48.1

51.3

54.5

57.7

60.9

64.1

70.5

72.4

73.7

80.1

Kg/Hr = .454 x Lbs/Hr Kw = .333 x Lbs/Hr Amps (1Ph) = Kw x 1000÷ V

olt.

Amps (3Ph) = Kw x 1000÷ (V

olt.(s) x 1.732)

Min Circuit

Ampacity = 1.25 x Rated Electrode

Amps

(Note: With RDU,

add .5

Amps @ 208/240v; add .25

Amps @ 480v)