Herrtronic MD Suggested Specifications

Part 1 - SCOPE

1. Furnish a humidification system for the project known as

___________________:_____________ ft. long x __________ ft.

wide x ___________ft. high.

2. Select a system that will maintain (automatically) _______%

R.H. at _______°F with a tolerance of +/- _____% R.H.

3. Warrant the system (except the replaceable steam cylinder) for

a period of two years from the date of shipment.

4. Provide an installation/operation/maintenance manual (for startup,

maintenance and diagnostics).

Part 2 – PRODUCT

The Herrtronic MD System shall consist of:

1. A self-contained electrode steam humidifier having a capacity of

______ lbs/hr. (or kg/hr.) with electrical characteristics of _______

VAC/_______ Ph./_______ Hz. The humidifier shall be capable of

operating on water with a conductivity of 70-1000 micromhos

automatically.

2. A humidity control system utilizing one of the following control

modes (shown with corresponding input method):

• On/Off (Humidistat)

• Proportional (Controller or signal-ohms/ VDC/ mADC)

• Proportional + Integral (Sensor or signal – VDC, mADC)

The control mode selection is integral with the Herrtronic MD unit.

The input devices shall be:

A. Control input device or signal _______

B. High limit humidistat _______ OR Proportional high limit device (or

signal) _______. NOTE: This enables modulating control systems

(“Proportional” or “Proportional + Integral”) to adapt the capacity

setpoint in response to varying psychrometric conditions – i.e.,

VAV systems, applications with high percentages of outdoor air,

etc.

C. Air proving switch_______NOTE: Air proving switch is standard on

“Room Distribution Unit.”

3. A steam distribution system consisting of:

A. Stainless steel steam distributors (for horizontal or vertical

installation) with integral pitch OR Room Distribution Unit (RDU)

with adjustable speed control. The supply blower shall operate

approximately 15 minutes after unit shutdown. Steam input shall

be thru the bottom or back of the unit. The RDU shall be remote/

unit mounted. The humidifier shall provide supply voltage and

control.

B. _______ ft. of EPDM steam hose OR _______ft. of insulated

copper pipe shall be provided for connection between the unit

and the steam distribution system NOTE: This system operates at

atmospheric pressure. Consult the factory if duct static pressure

exceeds 5” (MDM units) or 7” (MDS or MDD units).

4. An integral microprocessor control, monitor and diagnostic system.

The microprocessor shall:

A. Sense water conductivity and adjust water level and output

capacity.

B. Provide programmable setpoints with built-in default values for

simplified start-up. Only setpoints pertinent to the control mode are

accessible. Certain setpoints shall be password secured to prevent

tampering HERRTRONIC MD SUGGESTED SPECIFICATIONS

C. Provide adjustable drain tempering capability.

D. Include an LCD display (for longer life and easier viewing) – (2)

lines, 20 characters per line – to monitor system operation/

performance. Only parameters pertinent to the specific control

mode shall be displayed.

E. Provide “fault” sensing and display the type of fault. Certain faults

shall result in system shutdown. Other faults reflect a potential

maintenance problem and allow the unit to continue operation.

F. The humidifier shall also have (3) LED indicators to display:

a. Cylinder Full (Yellow)

b. Power(Green)

c. Fault (Red)

G. Network with up to (29) slave units (other MD control boards). The

master shall be capable of providing operational information on

any of the slave units individually.

5. Terminal connection points for all line and low voltage (control)

connections. A system on/off switch shall be externally available. A

door interlock switch shall prevent operation when the access door

is open.

6. Multiple cylinder humidifiers (Series MDD, over 110 lbs/hr.) shall

have separate fill, drain and microprocessor control provisions.

These units shall be capable of common or independent control.

7. Unit shall have a powder coated steel cabinet with lockable

cylinder access and electrical compartment access doors. The

glass filled polypropylene cylinder shall be easily replaced.

Electrode wiring shall be connected with nut/lockwasher

combination to prevent loosening of the connection (Friction

connections are not acceptable).

Part 3 – INSTALLATION

The installing contractor shall assume responsibility according to the

installation manual, specifically;

A. Application with system limitations.

B. Mounting recognizing clearances.

C. Provide water supply (including softened water) in accordance with

pressure and conductivity criteria. Hot, RO, DI water shall not be

applied.

D. Provide cylinder and cabinet drains.

E. All wiring in accordance with applicable sections of national,

state and local electrical codes. The contractor shall provide and

install external overcurrent protection and install system wiring in

accordance with the manufacturer’s requirements.

PART 4: SOURCE