Herrtronic md accessories, Herrtronic md room distribution unit, Herrtronic – Herrmidifier Herrtronic MD Engineering Guide User Manual

Page 9: Md series

Advertising
background image

Herrtronic

®

MD Series

E n g i n e e r i n g G u i d e

9

www.herrmidifier-hvac.com

Model #

(1)

Electrical Characteristics

Capacity

RDU-D-1

(2)

208-240-1-50/60

5-50 lbs/hr

RDU-D-1T

(2)

480-600-1-50/60

RDU-D-2

(3)

208-240-1-50/60

60-100 lbs/hr

RDU-D-2T

(3)

480-600-1-50/60

Notes:

1. Condensate return required; ¼” O.D. tubing (20 feet provided)

2. One Steam Inlet

3. Two Steam Inlets. 100-100 lbs. with > 380V only

4. RDU can not be direct mounted on MDM units

Approximate dimensions: 17”W x 15.5”D x 10”H

Adjustable speed blower

Integral air proving switch

15 minute blower-off delay

Unit includes air proving switch

Supply and control power from humidifier

STEAM PLUME

(@75º F, 55% R.H.)

Output

lbs/hr

Throw (in.)

Blower Speed

Breadth (in.)

Blower Speed (CFM

Rise (in.)

Blower Speed (CFM)

1

(210)

2

(240)

3

(280)

4

(320)

5

(365)

1

(210)

2

(240)

3

(280)

4

(320)

5

(365)

1

(210)

2

(240)

3

(280)

4

(320)

5

(365)

100

126

138

156

60

60

48

120

50

25

90

136

144

156

58

52

46

72

36

20

80

130

138

156

48

42

40

52

24

16

70

126

132

138

42

40

36

36

20

12

60

120

126

130

134

36

34

28

28

58

30

14

6

50

112

112

116

120

120

40

36

36

36

30

36

22

12

6

40

98

92

90

94

100

36

36

36

32

26

18

12

5

30

90

80

75

70

60

28

26

24

24

24

10

20

50

35

30

35

35

20

20

18

18

18

10

10

15

15

15

Herrtronic MD Accessories

• Steam Distributor Pipe – constructed of 304 stainless

steel; available in 12” to 72”; for horizontal and vertical

installation; inherent pitch to return condensate to unit.

• Control Devices – duct or space application; “on/off,”

“proportional,” and “proportional + integral” available

when controls required for application

• CS Series distribution grids available for quick evapora-

tion distances.

• Steam Hose – 2-ply EPDM rubber; 1-1/2” or 2” I.D.

• “Y” Connector, EST-255 – convert single outlet unit to

accommodate two steam distribution pipes.

• Drain Pump – removes condensate when gravity drain

is not convenient.

• Condensate Separator, EST-250 – drain condensate

from low spots in steam hose between unit and steam

distributor

• Air Proving Switch – pressure differential switch; as-

sures airflow prior to unit operation

Herrtronic MD Room Distribution Unit