or reverse osmosis water applications rarely require the

Auto DRN feature to be enabled as the water contains

very low dissolved solids.

• DRN Int – Drain Interval is the interval at which the unit

will initiate a timed drain. The default interval is factory

set at 24 hours.

• DRN Time – Drain Time is the amount of time the drain

valve will remain open if a timed drain is active. The

DRN Time is factory set at 5 minutes.

• Skim Time – Skim Time is the amount of time the unit

will continue filling to skim the surface of the water every

time a fill cycle is active. This feature may be set to zero

if the system is operating with very clean water; such as

de-ionized water. The factory Skim Time is 60 seconds.

Low water pressure may require that this setting be

increased so that the unit will skim.

• DRN Tmpr – Drain Tempering will activate the fill valve

anytime the drain valve is active. This feature acts to

lower the drain water temperature by diluting the drain

water with cold fill water. Water ensuing from the

skimmer port on the tank is not tempered. An external

drain water tempering device may be required. Please

consult the factory for information about the Drain

Tempering Reservoir, available separately.

• Force DRN – Force Drain is used to manually initiate a

drain cycle. The drain valve will remain active until this

parameter is set to OFF by the operator.

• RETURN – Returns the operator to the Home screen.

Status Menu

The Status menu contains a list of system inputs/outputs that

may be monitored by the operator.

• Input – This displays the percentage of demand when the

unit is configured for Proportional only operation. The

demand signal is received from a building management

system or from a remote humidity controller. This

displays the controlled relative humidity percentage

when the unit is configured for stand-alone P+I control.

The signal is received from a humidity transmitter

mounted in the controlled environment.

• Output – This displays the percentage of maximum unit

output.

• AF Switch – This displays whether the air proving switch

is OPEN or MADE. OPEN indicates a lack of airflow.

MADE indicates that the switch contacts are closed

indicating that airflow is present.

• Contactor – This displays ON/OFF status of the main

power contactor. This is monitoring the status of the

auxiliary contact on the main power contactor.

• Drain Val. – This displays the ON/OFF status of the drain

valve output.

• Fill Valve – This displays the ON/OFF status of the fill

valve output.

• Full Water – This displays the OPEN/MADE status of

the upper water level float switch. Each time this switch

opens, the unit will act to refill the tank for continued

humidification if a demand is present.

• Low Water – Displays the OPEN/MADE status of the

lower water level float switch. This switch must be

MADE in order for the heating elements to be energized.

• HL Input – Displays the relative humidity percentage

being sensed by the High Limit humidity sensor.

This item will not show in the menu unless the unit is

configured for stand-alone P+I control. If the unit has a

High Limit humidistat in lieu of a transmitter, this menu

item will read High Limit and the status will read OPEN

or MADE to indicate the status of the humidistat (switch).

Setpoints Screen

The Setpoints Screen will only be visible on units that are

configured for stand-alone P+I control. The HOME screen

will display RES-I. This means that a control humidity sensor

and high limit humidity sensor need to be connected to inputs

1 & 2 of the control board. Please see the wiring diagram

appropriate for the unit model being installed.

• Hum. SP – The user may enter the control humidity

setpoint here. Default = 40%RH.

• Max HL% – The operator may enter the maximum

allowable duct high limit %RH here. Default = 80%RH

• HL Range – The High Limit range sets the percentage

offset where the unit will begin to throttle the unit output

proportionally between the Max. HL% minus the HL

Range. Example: If the Max. HL% is set to 80% and

the HL Range is 10%, the unit will be limited to 50% of

maximum output if the high limit duct sensor is reading

75% relative humidity in the duct.

• Max. Cap. – Maximum Capacity allows the operator to

limit the maximum unit output based on a percentage.

Example: If the unit has a maximum capacity of 90 lb/