Herrmidifier Herrmersion RE User Manual

Page 6

Advertising
background image

Herrmersion RE

I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

6

www.herrmidifier-hvac.com

6.50

16.00

5.00

4.00

Back View (Mirror the hole pattern on mounting surface)

Model Number

Shipping Weight Operating Weight

RESX-XXX-X-30

125 lbs.

237 lbs.

RESX-XXX-X-45

128 lbs.

240 lbs.

RESX-XXX-X-90

134 lbs.

246 lbs.

“X” denotes weight independent portion of model number

PLUMBING

To make the necessary connections for water fill, drain, and

overflow/skim; the following steps are required. Refer to the

illustration below for dimensional information regarding the

fill & drain connections.

18.13

3.31

2.29

6.05

2.63 REF.

Drain Connection

Supply Connection

1. Install an external shut-off valve between the water

supply and the humidifier for ease in servicing the unit.

2. Connect the water supply to the bottom of the unit using

1/4” push-to-lock fitting. Supply water line should be

sized so that line pressure loss is minimal.

3. A drain line should be extended from the drain

connection to a sanitary waste. A minimum 1” ID copper

tube is recommended. If PVC is used, local codes

may require lower drain water temperature; enable the

drain tempering feature (see the control section of this

manual).

4. The skim/overflow connection on the front of the tank only

needs to be connected if the humidifier is being supplied

raw water containing significant mineral concentrations.

Deionized or reverse osmosis (technical waters) may be

used and do not require the use of this feature. The

skimming cycle allows floating debris to leave the tank

through the overflow drain and will reduce maintenance

intervals.

5. If using the skimmer connection, a trap must be installed

in the line so that steam can not escape from the

skimming connection during operation.

STEAM DISTRIBUTION

Herrmersion units may be used with stainless steel duct

dispersion tubes for injecting steam directly into the ductwork.

A minimum of 3 feet downstream clearance is required

for many applications; however differing psychrometric

conditions may require a greater distance. If required, consult

the factory to design a guaranteed absorption Herricane –

CS Steam Distribution System.

Mount the unit as close to the dispersion tube as possible.

Use 1.5” Type L insulated copper whenever the length of run

exceeds 20 feet. Do not exceed a 30 foot run as the capacity

of the humidifier may be decreased by as much as 15% and

the increased static pressure could cause problems with the

fill system. The maximum duct static pressure is 5” W.C.

Any insulation inside the bulk evaporation zone (inside the

ductwork) should be removed.

Steam holes in factory supplied duct dispersion tubes are

located 2” from the mounting plate and are designed for a

maximum 1” thick duct wall. Consult the factory if special

hole locations are required.

Do not install or mount standard dispersion tubes in a vertical

position or in a vertical airflow application. Special dispersion

tubes are available from the factory for installations which

require vertically mounted tubes or horizontal tubes with

vertical airflow.

Advertising