Herrmersion RE

I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

9

www.herrmidifier-hvac.com

4"

RECOMMENDED

8"

RECOMMENDED

POWER SUPPLY:

1. MATCHES DATA PLATE

2. IS PROPERLY GROUNDED

3. CAN CARRY AT LEAST 125%

OF RATE AMP DRAW

4. DISCONNECT SUPPLIED BY

OTHERS.

MAKE SURE ALL HIGH VOLTAGE

ELECTRICAL CONNECTIONS

ARE TIGHT.

NO UNTRAPPED LOW SPOTS

IN STEAM SUPPLY.

AIR FLOW IS HORIZONTAL OR VERTICAL UPFLOW

*A SPECIAL PIPE IS REQUIRED FOR VERTICAL DOWNFLOW,

OR A VERTICAL DISTRIBUTOR PIPE IN A HORIZONTAL

AIR FLOW.

MAKE SURE ALL HIGH VOLTAGE

ELECTRICAL CONNECTIONS ON

STEAM CYLINDER ARE TIGHT

(15-20 in/lbs)

3/4" MIN. I.D./1" MAX O.D.

FLEXIBLE DRAIN CONNECTION

DURING FILL CYCLE CHECK TO SEE IF ANY

WATER IS DRAINING FROM UNIT. A LOT OF

WATER FLOWING OUT OF THE UNIT WOULD

INDICATE EXCESSIVE WATER PRESSURE.

REDUCE THROUGH METERING FILL SOLENOID

OR SUPPLY VALVE TO HUMIDIFIER. A SMALL

AMOUNT OF WATER IS NOT UNCOMMON.

6" MIN. LENGTH OF 1-1/4" MIN. I.D. COPPER LINE.

IF PVC IS USED, LOCAL CODES REQUIRE A LOWER

TEMPERATURE DRAIN WATER IS NOT UNCOMMON.

BALANCE OF DRAIN LINE TO BE 1" MIN. I.D.

WITH A MINIMUM PITCH OF 1/8" PER 12" OF RUN

ENSURE OVERFLOW PIPING IS INSTALLED

AND TIGHT IF USING RAW WATER. A 5-6” P-TRAP IS

REQUIRED TO ENSURE STEAM DOES NOT ENSUE

FROM THE OVERFLOW PIPING. OVERFLOW

IS NOT REQUIRED WITH DI/RO WATER. SKIMMING

MUST BE DISABLED IN THE CONTROL SETTINGS.

INSTALLATION CHECK LIST