Herrmersion RE

I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

18

www.herrmidifier-hvac.com

hr, the user may limit the unit to 80 lb/hr by setting this

to 89%.

• Low Hum. – This allows the operator to trigger a low

humidity alarm if the control humidity falls below a

certain value.

NOTE: Some units may be configured with High Limit

humidistats in lieu of proportional high limit devices. If the unit

is using a humidistat for the high limit device, the setpoints

menu will only contain Humidity SP and Low Hum. The other

items do not pertain to high limit humidistat operation.

Alarm Screen

The Alarm Screen allows the operator to check the status

of the system alarms. This screen can scroll through the

currently active alarms; as well as alarm conditions that have

returned to normal. The date/time of the alarm is recorded

when the alarm goes active and when the alarm returns to

normal. Some alarms will lock out the unit and will require a

manual reset. This is performed by turning the unit ON/OFF

switch to the OFF position, waiting until the red LED goes out,

and then returning the switch to the ON position. Timed Drain

operations will illuminate the alarm LED. The drain will show

up as an active alarm while the unit is draining and return to

normal upon completion of the drain cycle. This allows the

control system to date/time stamp the drain operation so the

user may refer to it if needed. Upon completion of the timed

drain the unit will return to normal operation.

Clockset Screen

The Clockset Screen allows the user to adjust the system

clock. Time is only used for logging alarm times, so accurate

system time is not critical to proper system operation. The

DST link on this screen allows the user to set-up the day-light

saving time start and stop dates. It is recommended that the

date/time be set and confirmed before operating the unit.

UserPW Screen

Upon attempting to change parameters or set-points, the

control system will prompt the user for a password. The

USER password is 1111 by default. Logging into the keypad

as the USER will allow any of the items in the Parameters

Menu or the Set-points Menu to be changed by the user. The

CONFIG menu is typically for factory use only and should not

be modified by any operator without guidance from factory

technical personnel or a factory trained service technician.

If the ADMIN has logged into the system he may set a new

user password. The ADMIN password is 2222 by default.

Again, items in the CONFIG menu should not be changed by

untrained personnel.

Config Screen

The Configuration Screen allows the operator to adjust

system parameters that the typical operator usually would not

need to adjust under normal circumstances. The unit type

may be selected as P or I. A “P” unit operates according to