Herrmidifier Herrmersion RE User Manual

Page 19

Advertising
background image

Herrmersion RE

I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

19

www.herrmidifier-hvac.com

a 0-5VDC demand signal sent from another control system;

such as a building management system or DDC controller.

A unit configured for “I” is ready to accept 0-5VDC input

signal(s) from a humidity transmitter and a high limit humidity

transmitter. The unit will then modulate the unit according to

the setpoint entered by the operator.

• P/I Control – The Administrator may change the unit

control type so that the unit will react to a demand signal

from an external control system or the unit can control

itself according to an operator setpoint by reacting to a

signal from a humidity transmitter connected directly to

the control board.

• Overfill – The Administrator may adjust the length of a

fill cycle using this configuration parameter. Default =

60s. This is the length of time the fill valve will remain

open during a fill cycle plus the skim time set in the

Parameters menu.

• Interval – This allows the Administrator to change the

interval at which the PID loop calculates and updates the

unit output. Default = 60s. Increasing this time will slow

down the reaction time of the unit. Decreasing this time

will cause the unit to react faster to changes in humidity

level.

• P-Gain – The Proportional Gain adjusts the control band

in which the unit will begin to adjust capacity. As the

sensed humidity approaches the setpoint, the unit will

reduce the output percentage.

• I-Gain – The Integral Gain changes how the controller

will adjust the output percentage as time passes during

operation. If the setpoint is not achieved quickly enough,

increasing this gain will cause the unit to increase the

output percentage.

• Deadband – This may be adjusted to allow for a range

of input percentage or setpoint where no action is to be

taken. Default = 0%.

• Ramp Time – This Ramp Time allows the system to be

slowed by setting a minimum allowable time for the unit

to ramp from 0 to 100% output. Default = 0%.

Alarm Descriptions

The following alarm messages may appear. Refer to the

specific alarm message below for a description of what

circumstances will cause the alarm to become active.

• AF Switch Open: Upon a call for humidity or anytime

during the operation of the humidifier, if the air proving

switch opens, the unit will cease to produce steam until

the air proving switch closes again; indicating that airflow

is present again.

• EOS Drain: If a call for humidity is absent for greater

than 72 hours, the humidifier will drain the tank and

shutdown. Upon a new call for humidity, the unit will

refill the tank and commence normal operation.

• High Humidity: If the high limit humidity transmitter value

falls below the HL Fault setpoint (in CONFIG menu),

the unit will cease to produce steam. This will indicate

a problem with the sensor only. The default setting is

5% rh. This alarm can only become active on units

configured for proportional + integral control (RES-I).

• Low Humidity: If the controlled humidity falls below the

low humidity setpoint, the unit will cease to operate until

the problem is corrected and the alarm is acknowledged

and reset via the ON/OFF switch.

• Slow Drain: If during a timed drain cycle, the upper water

level float switch remains closed. This alarm will become

active thirty seconds before the end of the timed drain

cycle. The unit will cease to operate. The operator

should verify that the drain line is clear by invoking a

manual drain cycle. If the drain is open, the alarm may

be reset via the ON/OFF switch. The unit will return to

normal operation.

• Slow Fill: During any fill cycle, if both water level float

switches do not close within thirty minutes, this alarm

will become active. This may be caused by low water

pressure, an obstruction in the fill line, or a failed fill

solenoid valve. The unit will cease to operate until the

alarm is reset via the ON/OFF switch.

• Timed Drain: During any timed drain cycle, the alarm

light will illuminate for the duration of the drain cycle.

This is to provide indication only. The drain cycle will

be time stamped and stored in the ALARM screen of the

display module. No user intervention is needed. The unit

will commence normal operation upon the completion of

the drain cycle. Timed drain cycles may be deactivated

via the keypad.

• Water Lvl Err: This alarm indicates that the float switches

may be dirty and stuck open or closed. If the upper water

level float switch is closed and the lower water level float

switch is open, this alarm will become active. The tank

should be cleaned and the float switches checked for

proper operation. The alarm may be reset via the ON/

OFF switch.

Advertising