MK 2000A - Owner's Manual - Page 25

WARNING:

THE 2000A COMES SETUP FOR 208-230VAC SINGLE OR THREE PHASE

(SEE BELOW). FOR HOOKUP OF 480VAC 4 WIRE WYE PLUS GROUND YOU

WILL NEED A SPECIAL PLATE. CONTACT MK PRODUCTS TECHNICAL

SERVICE FOR INSTRUCTION.

Regardless of what type of input power that you use for the MK2000A,

you must provide a protected line (fused) disconnect in accordance with

all applicable electrical codes. The MK2000A is equipped with an internal

primary switch, but no fuses are provided. Line fuses should be 60 ampere

maximum (Buss non-60 recommended). Connection cables must be sized to

conform to national and local electrical code requirements.

Section 7 INPUT POWER CONNECTIONS

GROUND

#12 green

wire

CUSTOMER PROVIDED FUSED

DISCONNECT

NON-SHARED

Rear connection panel on MK2000A

X Y Z

NEUTRAL

When connecting Single (1) Phase

208-230VAC, you will use only the X, Y and

Ground terminals, DO NOT use the Z or

NEUTRAL terminal with this input power.

1 PHASE 208-230 VAC

208-230 VAC ONLY

SINGLE OR 3 PHASE

GROUND

#12 green

wire

X Y Z

NEUTRAL

Rear connection panel on MK2000A

CUSTOMER PROVIDED FUSED

DISCONNECT

NON-SHARED

When connecting 3 Phase 208-230VAC, you

will use the X, Y ,Z and Ground terminals,

DO NOT use the NEUTRAL terminal with

this input power.

3 PHASE 208-230 VAC

208-230 VAC ONLY

SINGLE OR 3 PHASE