Appendix A - Termination Locations

A = clearance to the termination frame above grade, veranda, porch,

deck, or balcony [16 inches (41 cm) minimum]

B = clearance to door, or sides and top of window, that may be opened

[16 inches (41 cm) minimum for appliances 100 000 BTU/H

(30kW)]

C = clearance to bottom of window that may be opened horizontally

[36 inches (92 cm) minimum for appliances 100 000 BTU/H

(30kW)]

D = no clearance to permanently closed window when installed with

approved glass penetration termination

E = clearance to permanently closed window [16 inches 41 cm recom-

mended to prevent condensation on window]

F = vertical clearance to ventilated soffit located above the termination

within a horizontal distance of 2 feet (61 cm) from the centreline of

the termination [22 inches (56 cm) minimum]

G = clearance to unventilated soffit

[16inches (41 cm) minimum to non-combustibles]

[22 inches (56 cm) minimum to combustibles]

H = clearance to outside corner [9 inches (23 cm) minimum]
I = clearance to inside corner [12 inches (31 cm) minimum]
J = * not to be installed above a meter/regulator assembly within

40" (103 cm) horizontally from the centreline of the regulator

K = clearance to service regulator vent outlet [3 feet minimum in the

United States] [*6 feet (1.8 m) minimum in Canada]

L = clearance to nonmechanical air supply inlet to building or the

combustion air inlet to any other appliance [16 inches (41 cm)

minimum for appliances 100 000 BTU/H (30kW)]

M = clearance to mechanical air supply inlet

[*6 feet (1.8 m) minimum]

N =

clearance above paved sidewalk or a paved driveway located

on public property [*7 feet (2.1 m) minimum]

P = clearance under veranda, porch, deck, or balcony

[16 inches (41 cm) minimum

to non-combustibles]

[22 inches (56 cm) minimum

to combustibles]

Q = clearance above a roof [24 inches (61 cm) minimum]
R = clearance to adjacent walls and neighbouring buildings

[18 inches (46 cm) minimum]

S = clearance from corner in recessed location

[12 inches (31 cm) minimum]

T = maximum depth in recessed location

[48 inches (122 cm) minimum]

U = minimum width for back wall of recessed location

[24 inches (61 cm) minimum]

V = no horizontal clearance between the frames of two terminations

that are level.

W = horizontal clearance between the frames of two terminations

that are not level. [36 inches (92 cm) minimum]

a vent shall not terminate directly above a sidewalk or paved

driveway which is located between two single family dwellings

and serves both dwellings

only permitted if veranda, porch, deck, or balcony has an open

side that is equal to or greater than the depth of the enclosed

area

* as specified in CGA B149 Installation Codes. Note: local Codes

or Regulations may require different clearances