ONICON FB-3500 Series User Manual

Page 10

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
FB-3500 Bi-Directional Insertion Electromagnetic Flow Meter Manual 05/14 - 0718-3

Page 10

SECTION 3.0: INSTALLATION, REMOVAL AND ADJUSTMENT

WARNING

Insertion flow meters may be installed in pipes which are under high pressure. Accidents with

these systems can cause serious injury or death. Only persons experienced with high pressure

systems and related knowledge in the heating, cooling and fluid metering fields should attempt

to install, adjust, or remove the flow meter. Please read all instructions before attempting to

insert or remove a flow meter.

!

ONICON will be happy to assist with technical recommendations and to provide guidance by
telephone or e-mail. On-site field engineering, installation and service is also available at additional cost.

3.1 INSTALLATION SITE SELECTION

Install the flow meter where it will be accessible for personnel to perform necessary periodic
maintenance. The clearance required for installation is typically 30”- 40” from the pipe wall to
the nearest obstruction above the valve assembly. This clearance dimension will increase with
large diameter pipes. The environment should be free of corrosive liquids/fumes, temperature
extremes and heavy vibration. The following diagrams should be used as a guide to the proper
location for installing the meter.

3.1.1 General Site Selection Guidelines

GENERAL PRACTICES:

1.

For best results, install the flow meter in a straight run of pipe, free of bends, tees,

valves, transitions and obstructions.

2.

Straight run recommendations vary based on the nature of the upstream obstruction.

See the table below for guidelines in determining upstream straight run

recommendations based on the nature of the obstruction. Please note that depending

upon specific location details, more or less straight run may be required to produce a

satisfactory flow profile.

For 3” and larger pipe diameters

Obstruction on either side of meter

Straight run distance recommended

between meter and obstruction

Single bend preceded by ≥ 9 diameters of
straight pipe

10 Diameters

Pipe size reduction / expansion in straight
pipe run

10 Diameters

Single bend preceded by ≤ 9 diameters of
straight pipe

15 Diameters

Outflowing tee / pump outflow

20 Diameters

Multiple bends out of plane

30 Diameters

Inflowing tee

30 Diameters

Control / modulating valve

30 Diameters

Advertising
This manual is related to the following products: