Tools needed for standard installation:

• 1

5

/

16

” wrench or adjustable wrench

5

/

8

” wrench or small adjustable wrench

• pipe wrench (to hold valve in place)
• pipe thread sealant

CAUTION

If there are any leaks around the clamping nut or stem, DO NOT ATTEMPT TO STOP THE

LEAKAGE BY OVERTIGHTENING THE CLAMPING NUT. Damage to this nut or the clamping

ring under the nut may prevent the assembly from properly holding the meter in the pipe. The

clamping nut is not part of the sealing mechanism. Any leaks in this area indicate that the “O”

ring is not sealing properly and you must contact ONICON for assistance.

WARNING

When you are ready to refill the system, make sure that all lines are filled with water before

inserting the meter into the flow stream. If the lines are not filled and this is a hot water

system, some water may flash to steam and exceed the high temperature limit for the sensor

head assembly. This flash over could also exceed the pressure ratings of the meter and the

assembly could fail allowing steam and hot water to escape causing serious injury.

!

3.2.6 Installing the Flow Meter

Flush, fill and pressure test the piping system prior to installing the meter. Loosen

clamping nut to facilitate installation.

Clamping nut

Keep sensor

head fully

withdrawn

during

installation.

Apply paste or

Teflon tape as

necessary.

Thread hot

tap adaper on

to ball valve

and tighten as

necessary.

Maintain a firm

grip on the

enclosure when

opening valve.

Crack

valve to

test for

leaks.

!