System-10-N2 BTU Meter Installation and Operation Guide 05/14 - 0655-5 / 18322

Page 12

SECTION 2.0: POINT FILE (.ddl)

2.1 ddl OR POINT FILE

The System-10 BTU Meter operates in one of three operating modes: single, dual or bi-directional.

The dual and bi-directional modes utilize the same .ddl files. The tables below contain point

information for each of the operating modes.

The .ddl file contains the information that identifies the device to the N2 supervisory controller.

It also specifies the variables that are available to be transmitted to and from the device on the

network.

The tables below contains .ddl file information

2.1.1 Single Mode Point Information

In single mode operation, only one register accumulates energy and one register

accumulates volume.

NPT

1

NPA

2

UNITS

POINT DESCRIPTION

RANGE/VALUE

AI

1

Selectable

(See Energy Rate

Table)

Energy Rate

0 - 999,999

AI

2

Selectable

(See Volume Rate

Table)

Volume Rate

0 - 999,999

AI

3

Deg F

Supply Temperature

0.0 Deg F - 500.0 Deg F

AI

4

Deg F

Return Temperature

0.0 Deg F - 500.0 Deg F

BI

1

None

Dual Mode Status Indicator

- Heating (supply > return)

- Cooling (supply < return)

OR

- Forward flow

- Reverse flow

(Refer to Section 3.3.3 of

System-10 manual for flow

direction information.)

0 - Heating

1 - Cooling

0 - Forward

1 - Reverse

ADF

1

Selectable

(See Energy Total

Table)

Mode 1 Energy Total

0 – 999,999

ADF

2

Selectable

(See Volume Total

Table)

Mode 1 Volume Total

0 – 999,999

ADF

5

User Defined

Auxiliary Pulse Input Sum (Di3)

0 – 999,999

BO

1

None

Reset (Zero)

Energy Total, ADF-1

OVERRIDE

Binary Output,

Object 1 - ON