ONICON System-10 N2 User Manual

Page 17

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10-N2 BTU Meter Installation and Operation Guide 05/14 - 0655-5 / 18322

Page 17

2.1.4 SAMPLE .ddl FILES

Single Mode Meter .ddl File

SAMPLE SINGLE MODE .ddl FILE

*****************************************************************

* ONICON, SYSTEM-10 BTU Meter: SERIAL NUMBER: XXXX

* PROGRAM VERSION: X.X

* Metasys-N2 Address: xxxx

* Single Mode

* This .ddl file is device specific to the above serial number.

*.This data is valid at the time of creation (07/23/2004 1:00 pm)

* And can be rendered invalid due to field changes in units

* or multipliers.

*

@MODEL+

CSMODEL “ONICON”,”VND”

*

AITITLE “Analog Inputs”

BITITLE “Binary Inputs”

ADTITLE “Analog Data Points”

BOTITLE “Binary Outputs”

*

ANALOG INPUTS COS AVAILABLE.

CSAI “AI1”,N,N,”ENRATE”,”10KBTU/HR”

CSAI “AI2”,N,N,”VORATE”,”10GPM”

CSAI “AI3”,N,N,”TMPSPLY”,”DEGF”

CSAI “AI4”,N,N,”TMPRTN”,”DEGF”

*

* BINARY INPUT COS AVAILABLE.

CSBI “BI1”,Y,Y, “MODEIND”,”N/A”

*

* N2 READS ADF1, ADF2 FOR ENERGY AND VOLUME TOTALS.

CSAD “ADF1”,N,N,”ENERTOT”,”10KBTU”

CSAD “ADF2”,N,N,”VOLMTOT”,”10GAL”

CSAD “ADF5”,N,N,”CNTSTOT”,”PLSSUM”

*

* NEVER MAP OUTPUT POINTS IN A CS MODEL AS DISCRETE OBJECTS.

* RESET VOLUME AND ENERGY TOTALS WITH COMMAND OVERRIDE BO ON

CSBO “BO1”,Y,Y, “RSTENTOT”,”N/A”,”reset”

CSBO “BO2”,Y,Y, “RSTVLTOT”,”N/A”,”reset”

CSBO “BO5”,Y,Y,”RSTAXTOT”,”N/A”,”reset”

****************END SINGLE MODE DDLFILE***************************

Advertising