System-10-N2 BTU Meter Installation and Operation Guide 05/14 - 0655-5 / 18322

Page 5

SECTION 1: INTRODUCTION

1.1 PURPOSE OF THIS GUIDE

The purpose of this guide is to provide installation and commissioning procedures and basic

installation and operating instructions for the ONICON System-10-N2 serial interface.

1.2 TYPICAL SYSTEM-10 NETWORK INTERFACE MODULE

ONICON’s System-10 is a true heat (Btu) computer which accepts data from several sensors,

performs a series of computations with that data, and displays and/or transmits the results as an

indication of the amount of heat (Btu’s) being transferred per unit time or as a totalized amount.

It can also be provided with an optional Metasys

®

N2 serial interface to communicate data to the

building control network.

1.3 SPECIFICATIONS

METASYS

®

N2 NETWORK INTERFACE

N2 RS485

Transceiver: 2-wire, half-duplex

Device address range: 1 – 255 (Default: 017)

Baud rate: 9600

Termination: none

Biasing: none

24 VAC Input

Metasys

®

N2 Communications

to Johnson Controls System

Heat Exchanger

Return

Supply

SYSTEM-10

BTU METER

Return Temp

Sensor

Supply Temp

Sensor

ONICON insertion

flow meter

(purchased separately)

SCROLL RESET PROGRAM

BTU X 10,000