D-1400 Portable Metereing System Manual 05/14 - 0722-2

Page 22

5.2 TROUBLESHOOTING GUIDE FOR D-100 DISPLAY

NOTE: Also refer to the COMMISSIONING GUIDE located on the preceding pages.

Reported Problem

Possible Solutions

Flow rate is indication zero flow.
(When fluid is flowing in the pipe.)

• Verify that the correct supply voltage is

present at the flow meter power input.

• Verify that the flow meter signal outputs

are properly wired to the display.

• For insertion meters, verify that the

meter is correctly inserted and parallel

with the pipe.

• For turbine meters, verify that the turbines

are not clogged with debris.

• Re-confirm that there is really flow in the
pipe.

Displayed flow rate is too high or too low.

• Verify that the serial number of the flow

meter matches the serial number shown

on the label inside the D-100 front cover.

• Verify that the correct supply voltage is

present at the flow meter power input.

• Verify that the pipe diameter matches the

diameter shown on the calibration

certificate and on the flow meter tag.

• For insertion meters, verify that the

meter is correctly inserted and parallel

with the pipe.

• For turbine meters, verify that the turbines

are not clogged with debris.

Ai3 and/or Ai4 sensor values are too high or
too low.

• Verify that the sensor scaling matches

that programmed values shown on the

label inside the D-100 front cover and on

the calibration certificate.

• Confirm that the control system is

correctly scaled.

Data is not available at the control system.

• Verify network addresses are properly

programmed into the D-100.

• If applicable, verify the Baud rate.
• Check the polarity of the network
connections.

For technical assistance, contact ONICON Incorporated at (727) 447-6140.