SECTION 2.0: POINT FILE (.ddl)

The D-100 Display operates in one of two operating modes, unidirectional or bidirectional flow. The

tables below contain point information for each operating mode.

The .ddl file contains the information that identifies the device to the N2 supervisory controller. It also

specifies the variables that are available to be transmitted to and from the device on the network.

The tables below contain the .ddl information.

2.1 UNIDIRECTIONAL FLOW POINT INFORMATION

Point Type

& Address

Engineering Units

Point Description

Range

AI2

Selectable (See volume/
mass rate table)

Volume or mass rate

0-999,999

AI3

User defined

Generic analog input

0-999,999

AI4

User defined

Generic analog input

0-999,999

ADF2

Selectable (See volume/
mass total table)

Volume or mass total

0-9,999,999

ADF5

User defined

Auxiliary pulse input total (Di3) 0-9,999,999

BO2

None

Reset total for ADF2

OVERRIDE Binary
Output, Object 2-ON

BO5

None

Reset total for ADF5

OVERRIDE Binary
Output, Object 5-ON

2.2 BIDIRECTIONAL FLOW POINT INFORMATION

Point Type

& Address

Engineering Units

Point Description

Range

AI2

Selectable (See volume/
mass rate table)

Volume or mass rate

0-999,999

AI3

User defined

Generic analog input

0-999,999

AI4

User defined

Generic analog input

0-999,999

ADF2

Selectable (See volume/
mass rate table)

Mode 1 volume or mass total

0-9,999,999

ADF4

Selectable (See volume/
mass rate table)

Mode 2 volume or mass total

0-9,999,999

ADF5

User defined

Auxiliary pulse input total (Di3) 0-9,999,999

BI1

None

Flow Direction Indication

0-Forward
1-Reverse

BO2

None

Reset total for ADF2

OVERRIDE Binary
Output, Object 2-ON

BO4

None

Reset total for ADF4

OVERRIDE Binary
Output, Object 2-ON

BO5

None

Reset total for ADF5

OVERRIDE Binary
Output, Object 5-ON