ONICON D-100 N2 User Manual

Page 16

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
D-100-N2 Network Interface Installation Guide 05/14 - 0659-4 / 18344

Page 16

Energy Rate

KBTU/H

1

KBTUH

KW

1

KW

TONS

1

TONS

Volume Rate

GPM (Gal/Min)

1

GPM

L/S (L/Sec)

1

LPS

M3H (M

3

/Hr)

1

M3H

CFS (Ft

3

/Sec)

1

CFS

CFM (Ft

3

/Min)

1

CFM

None (Not defined in N2)

Any

Any

Any

2.7 AUXILIARY PULSE (Di3) TOTAL (ADF5)

D-100 LCD Display

Engineering Units

D-100 Display Multiplier

Point File Engineering Units

Description

User defined text entry

1

User defined text entry

2.6 SAMPLE .ddl FILES

Sample Unidirectional Mode .ddl File

*****************************************************************

* ONICON, D-100 Display: SERIAL NUMBER XXXXXX

* PROGRAM VERSION: DM2.022

* Metasys-N2 address: XXX

* Unidirectional Mode

*

* This DDL file is device specific to the above serial number

* This data is valid at time of creation (07/20/2005 05:27:42 PM) and can be rendered invalid due

* to field programming changes to engineering units or multipliers.

*****************************************************************

@MODEL+

CSMODEL “ONICON”, “VND”

*

AITITLE “Analog Inputs”

ADTITLE “Analog Data Points”

BOTITLE “Binary Outputs”

*

* ANALOG INPUTS COS AVAILABLE

CSAI “AI2”,N,N,”VOLUMERT”,”GPM”

*

i

IMPORTANT NOTE

Auxiliary pulse input (Di3) totalizes pulses. The engineering units and multipliers associated

with the total are not defined by the D-100; they are defined by the pulse output of the meter

connected to the auxiliary pulse input.

E.g. a domestic water meter with a pulse output is connected to the auxiliary pulse input. The

water meter output is scaled to 100 gallons per pulse. ADF5 could be configured as: CSAD

“ADF5”,N,N,”WATERTOT”,” 100GAL”