ONICON D-100 N2 User Manual

Page 17

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
D-100-N2 Network Interface Installation Guide 05/14 - 0659-4 / 18344

Page 17

************* Unidirectional Mode Meters Only *********************

* N2 READS ADF2 FOR VOLUME or MASS TOTALS.

* NOTE UNITS MULTIPLIER

CSAD “ADF2”,N,N,”VOLUMTOT”,”10GAL”

*

*Reset Volume Totals with the command Override BO ON.

CSBO “BO2”,Y,N,”RST_VOL”,”n/a”,”reset”

*

***************** End Unidirectional Mode ****************************

Sample Bidirectional Mode .ddl File

*****************************************************************

* ONICON, D-100 Display: SERIAL NUMBER XXXXXX

* PROGRAM VERSION: DM2.022

* Metasys-N2 address: XXX

* Bidirectional Mode

*

* This DDL file is device specific to the above serial number

* This data is valid at time of creation (07/20/2005 05:27:42 PM) and can be rendered invalid due

* to field programming changes to engineering units or multipliers.

*

*****************************************************************

@MODEL+

CSMODEL “ONICON”, “VND”

*

AITITLE “Analog Inputs”

BITITLE “Binary Inputs”

ADTITLE “Analog Data Points”

BOTITLE “Binary Outputs”

*

* ANALOG INPUTS COS AVAILABLE

CSAI “AI2”,N,N,”VOLUMERT”,”GPM”

*

* BINARY INPUT COS AVAILABLE

CSBI “BI1”,Y,Y, “MODEIND”, “N/A”

************* Unidirectional Mode Meters Only *********************

* N2 READS ADF2, ADF4 FOR VOLUME or MASS TOTALS.

* NOTE UNITS MULTIPLIER

CSAD “ADF2”,N,N,”M1VOLTOT”,”10GAL”

CSAD “ADF4”,N,N,”M2VOLTOT”,”10GAL”

*

*Reset Volume Totals with the command Override BO ON.

CSBO “BO2”,Y,N,”RST_VOL”,”n/a”,”reset”

*

***************** End Bidirectional Mode ****************************