11. Technical Specification

Specifications for 120VVAC /277VAC

Capacity (W)

Description

500

750

1000

1250

1500

2100

Input

Voltage

Single Phase 120Vac or 277Vac

Voltage Range

120Vac ±10% or or 277Vac

Frequency

60Hz +/- 4Hz

Output

Voltage (on battery)

Single Phase 120Vac or 277Vac

Voltage Range

120Vac ±2% or 277Vac

Frequency (on battery)

60 Hz +/-0.5%

Transfer Time

0 ms

Overload Recovery

Auto transfer to UPS

High Efficiency mode (AC to AC)

> 95 %

UPS Design Technology

On-Line / Fully digitized microprocessor controlled

Output Wave Form

Sine wave

Harmonic distortion

< 3% of T.H.D. at linear load

Protection and
Filtering

Overload Protection

125% for 1 minutes and 150% for 10 seconds

Short Circuit Protection

Circuit breaker

System/Display/
Warning

Visual Display

(LED model)

UPS on(green), line-mode(green),

battery mode(yellow), bypass(yellow), fault(red)

Visual Display

(LCD model)

Input / output voltage, input / output frequency,

on-line mode, back up mode, battery capacity, load

level

Audible Alarm

(Battery back-up)

Beep every 5 sec

UPS Fault

Continuous beeping sound and LCD display

Communication

RS-232 Serial Port and USB

Battery

90 min. UL924

(Sealed, maintenance

free lead acid battery

8X26 A/H 8X35 A/H

8X35 A/H

8X50 A/H

8X65 A/H

8X65A/H

Dimensions

(Inches) Width x Height x Depth

23.5 X 34.25 X 18.25

Environmental

Operating Temperature

0 - 40ºC / 32 ~ 104ºF

Storage Temperature

-20 ~ 50ºC / -4 ~ 122ºF

Audible Noise

(1 meter from surface)

< 40 dBA

Relative Humidity

0 ~ 95% humidity, non-condensing

Note: Due to continuous improvement, specifications are subject to change without prior notice.