OnLine Power Power Wave 4 User Manual

Page 35

Advertising
background image

6005-145 Rev. A

1-24

FUSE/TEMP –Inverter fuse is blown or over temperature condition

exists.


OVERLOAD –
output is overloaded by over 110%, 125% or 150%.

HIGH DC – the LED will light as long as the DC voltage is over

430VDC.

BAT LOW – the LED will light as long as the DC voltage is lower than

320VDC.

BAT LOW STOP – the LED will light as long as the DC voltage is lower

than 295VDC, inverter cannot start.

FAULT – the inverter is shutdown due to abnormal conditions such as

overload, short circuit, high DC, fuse over temperature, bypass
breaker on or emergency stop.

Since these LEDs are located behind the transparent window, the user can
see them clearly without opening the door.

D: Audible (buzzer) alarm: The user should not be expected to watch the ELI

all the time. Therefore, when abnormal conditions occur, an audible sound
should be emitted to warn the user to check the status of the ELI. The alarm
buzzer will beep under any one of the following conditions:

INVERTER IS OVERLOADED-

>110%, beep once / 3 seconds

>125%, beep once / second

>150%, beep twice / second

BACK- UP

>320VDC, beep once / 3 seconds

<320VDC, beep twice / second

<295VDC, no beeping

INVERTER IS SHORT CIRCUITED - beep continuously

FUSE BROKEN - beep continuously

HEAT SINK OVER TEMPERATURE - beep continuously

HIGH DC SHUTDOWN - beep continuously

BYPASS ON STOP - beep continuously

EMERGENCY STOP – (emergency power off) beep continuously

The buzzer will also beep once every time the inverter is switched on or
off to acknowledge to the user that his key is valid and accepted.