OnLine Power Power Wave 4 User Manual

Page 64

Advertising
background image

6005-145 Rev. A

5-11

When CHARGE CURRENT is selected, the values that can be selected will be
shown (LO/ME/HI). When the batteries are being boost-charged for whatever the
reason, the charging current will be limited by a value according the setting in this
row. The current value (or the being selected) will flash, and is confirmed by the
ENTER (←┘) key.

The value can be selected by a rules listed below:

BACK-UP TIME SETTING

10 – 30 MIN LO

30MIN – 1HOUR ME

> 1 HOUR HI

If “EXIT” is selected (blinking instead of pointed by cursor), the screen will go back
to the MENU 5- the PARAMETER SETTING menu.

5.12. Menu 11 – Date/Time Setting Menu

< D A T E T I M E S E T T I N G >

→ Y E A R = X X X X H O U R ( 2 4 H ) = X X

M O N T H = X X M I N U T E = X X

D A Y = X X D A Y O F T H E W E E K = M O N E X I T


This menu is displayed when the item < DATE/TIME > is selected from MENU 5,
the PARAMETER SETTING menu. The user can change the YEAR/MONTH/DAY/,
HOUR/MINUTE/DAY OF THE WEEK of the real time clock through this menu.
Once this menu is opened, the present value in the real time clock will be shown. The
cursor (→) can be moved upward by the UP(↑) key, and can be moved downward by
the DOWN(↓) key to the item the user wants to change. The selection is confirmed by
pressing the ENTER (←┘) key. See the figure above. The values to be entered are
numbers except the DAY OF THE WEEK (MON, TUE… provided for user
selection). The values that can be entered are restricted to certain values according to
which item is being set (the values are listed below).