Interface connections – OnLine Power Power Wave 4 User Manual

Page 67

Advertising
background image

6005-145 Rev. A

6-1

6.

INTERFACE CONNECTIONS

All interfaces are connected from 3R PCB. See the figure below.

6.1. Dry Contacts

8 terminals of dry contacts are provided. These terminals are normally open (non-
conducting). When an event occurs, the terminal will close (conduct). Maximum contact
rating is 16A/250VAC(16A/30VDC). The events are shown below.

INVON – Closed whenever the inverter is on, open when the inverter is off.

OVL – Closed whenever the ELI is overloaded.