Troubleshooting, Outputs force, 13 modular service tool sd – Orion System Modular Service Tool SD User Manual

Page 13

Advertising
background image

TROUBLESHOOTING

13

Modular Service Tool SD

Analog Output 5 Screen

Mod Cooling Override

Analog Output #5

Override Volts: -1.0

[-1.0=Auto]

Analog Output 6 Screen

RA Damper Override

Analog Output #6

Override Volts: -1.0

[-1.0=Auto]

Analog Output 7 Screen

RA Bypass Override

Analog Output #7

Override Volts: -1.0

[-1.0=Auto]

VCB-X & VCC-X Controllers

Main Fan VFD Override Screen

Main Fan VFD

Override Volts: -1.0

[-1.0 = Auto]

The default setting for normal operation is -1.0 volts. Voltages between
0 to 10.0 can be set for any of the Analog Output Overrides. Press

<Enter>

after making a setting change and the next Analog Output

Override Screen will be displayed.

Economizer Override Screen

Economizer

Override Volts: -1.0

[-1.0 = Auto]

The default setting for normal operation is -1.0. Voltages between 0.0
and 10.0 can be set. Press

<Enter>

after making a setting change and

the next Analog Output Override Screen will be displayed.

Modulating Heat Override Screen

Modulating Heat

Override Volts: -1.0

[-1.0 = Auto]

Outputs Force

The default setting for normal operation is -1.0. Voltages between 0.0
and 10.0 can be set. Press

<Enter>

after making a setting change and

the next Analog Output Override Screen will be displayed.

Exhaust Fan Override Screen

Exhaust Fan Signal

Override Volts: -1.0

[-1.0 = Auto]

The default setting for normal operation is -1.0. Voltages between 0.0
and 10.0 can be set. Press

<Enter>

after making a setting change and

the next Analog Output Override Screen will be displayed.

Modulating Cool Override Screen

Modulating Cool

Override %...: -10%

[-10 = Auto]

The default setting for normal operation is -10 percent. Percentages
between 0 to 100 can be set. Press

<Enter>

after making a setting

change and the next Analog Output Override Screen will be displayed.

Modulating Condenser 1 & 2 Override Screens

(VCB-X Only)

Mod. Condenser 1 & 2

Override Volts: -1.0

[-1.0 = Auto]

The default setting for normal operation is -1.0. Voltages between 0.0
and 10.0 can be set.

Return Air Bypass Override Screen

Return Air Bypass

Override Volts: -1.0

[-1.0 = Auto]

The default setting for normal operation is -1.0. Voltages between 0.0
and 10.0 can be set.

Return Air Damper Override Screen

Return Air Damper

Override Volts: -1.0

[-1.0 = Auto]

The default setting for normal operation is -1.0. Voltages between 0.0
and 10.0 can be set.