Appendix a - save, load, copy setpoints, Restoring previously saved setpoints – Orion System Modular Service Tool SD User Manual

Page 15

Advertising
background image

Modular Service Tool SD

APPENDIX A - SAVE, LOAD, COPY SETPOINTS

15

Restore Setpoints - Network or

Stand-Alone Mode

The Restore Setpoints feature is used to reload a saved setpoints fi le
from one controller back to itself. This could be useful if setpoints or
confi gurations were changed and need to be reset.

You can perform this function on a networked system; however, the
Modular Service Tool needs to be directly connected to the controller
you wish to restore previously saved setpoints to.

From any menu screen, press

<BALANCE - TEST>

. The Unit Selec-

tion Screen will appear requesting that you enter the unit ID number of
the controller. Enter the network unit ID for the controller you want
to restore setpoints to. Example, 2 for Unit 2. Then press

<ENTER>

.

Once communication is established, *00* at the bottom right of the
screen will go away. After a brief pause, press

<

>

to get to the Bal-

ance - Test Screen shown below.

Outputs Force

Para Blocks
Save/Copy/Restore

Scroll down to the ‘Save/Copy/Restore’ option shown above and press

<ENTER>

. This will take you to the Save Setpoints Screen shown below.

Save Setpoints

Press Enter To Save

Press

<

>

four times to access the Restore Setpoints Screen shown

below.

Restore Setpoints

Press Enter to Load

Press

<ENTER>

. This will reload the setpoints from the saved fi le. You

will receive confi rmation that the setpoints were loaded successfully.

Restoring Previously Saved Setpoints

Advertising
This manual is related to the following products: