Soho Installation and Operation Manual

36 ______________________________________________________________________________

7.4.1

SHIELD CONSTRUCTION RULES

See figure Clearances for shield construction to match each letter to a clearance.

- Adhesives used in shield construction must not ignite or lose adhesive qualities at

temperatures likely to be encountered.

- Mounting hardware which extends from the shield surface into combustibles may be used only

at the edges of the shield.

- Mounting hardware must allow full vertical ventilation.

A Minimum clearance between the appliance top and an unshielded combustible ceiling:

1041 mm (41 in.)

B Shield extension above appliance: 500 mm (20 in.)

C Minimum space behind shield: 25 mm (1 in.). In Canada 21 mm (7/8 in)

D Clearance along the bottom of shield: minimum: 25 mm (1 in.) and maximum: 75 mm (3 in.)

E Minimum clearance along the top of shield at ceiling: 75 mm (3 in.)

F Mounting hardware must not be located closer than 200 mm (8 in.) from the vertical centre

line of the appliance.

G Edge clearance for ceiling shields to side and back walls: 75 mm (3 in.)

H Shield extension beyond each side of appliance: 450 mm (18 in.)